 |
|
| 1 |
All 240V hot tubs must be permanently connected (hard wired) to the power supply. 120V hot tubs may use GFCI cord, plugged into a grounded outlet. Supplying power to the hot tub which is not in accordance with these instructions will void both the independent testing agency’s listing and the manufacturer’s warranty. |
|
| 2 |
The power supplied to the hot tub must be a dedicated circuit with no other appliances or lights sharing the power. |
|
| 3 |
When determining the current, voltage and wire size required for the hot tub configuration to be connected, refer to manufacturer’s recommendations and keep these points in mind:
- Wire size must be appropriate per NEC and/or local codes.
- We recommend THHN copper core wire.
- All wiring must be copper to ensure adequate connections.
- Do not use aluminum wire.
- When using wire larger than #6, add a junction box near the hot tub and reduce to short lengths of #6 wire between the junction box and the hot tub.
|
|
| 4 |
The electrical supply for the hot tub must include a suitably rated switch or circuit breaker to open all ungrounded supply conductors to comply with Section 422-20 of the National Electric Code, ANSI/NFPA 70. The disconnecting means must be readily accessible to the hot tub’s occupant but installed at least 5 feet (1.5m) from the hot tub water. |
|
| 5 |
The electrical circuit for the hot tub must include a suitable ground fault circuit interrupter (GFCI) as required by NEC Article 680-42.
The disconnect must be readily accessible and visible to the spa occupant but installed at least 5 feet, measured horizontally, from the spa water. |
|